New
Generation of Digital Temperature Controller
|
|
o
Depth of only 78mm
|
|
o
Various temperature inputs: thermocouple, platinum
resistance thermometer,
|
|
infrared temperature sensor, and analog
inputs.
|
|
o
Auto-tuning and self-tuning are available. Auto-tuning is
possible even while
|
|
self-tuning is being executed.
|
|
o
Heating or heating/ cooling control is available
|
|
o
Start/ stop function
|
|
o
Conforms to UL, CSA and IEC safety standards as well as
CE marking.
|
|
Ordering
Information
|
|
E5CZ Standard Models
|
|
Size
|
Power
supply voltage
|
Number
of alarm points
|
Control
outputs
|
Heater
burnout alarm
|
Model
|
|
1/16 DIN
48 (W) x
48 (H) x
78(D) mm
|
100 to
240 VAC
|
2
|
Relay
|
No
|
E5CZ-R2
|
|
|
|
Voltage
(for driving SSR)
|
No
|
E5CZ-Q2
|
|
Specifications
|
|
#
Ratings
|
Supply
voltage
|
100 to
240 VAC
|
Operating
voltage range
|
85% to
110% of rated supply voltage
|
Power
consumption
|
7W (7VA)
|
Sensor
input
|
Thermocouple:
K, J, T, E, L, U, N, R, S, B
Platinum
resistance thermometer: Pt100, JPt100
Infrared
temperature sensor: 10 to 70ðC,
60 to 120ðC, 115 to 165ðC, 160 to
260ðC
Voltage
input: 0 to 50mV
|
Control
output
|
Relay
output
|
SPST-NO,
250VAC, 3A (resistive load), electrical life:
100,000
operations
|
Voltage
output
|
12 VDC
+15%/-20% (PNP), max. load current:21mA,
with short
circuit protection circuit
|
Alarm
output
|
SPST-NO,
250VAC, 1A (resistive load), electrical life:
100,000
operations
|
Control
method
|
2-PID
control or ON/OFF control
|
Setting
method
|
Digital
setting using front panel keys
|
Indication
method
|
7-segment
digital display and single-lighting indicator
Character
height: PV:10.0mm; SV:6.5mm
|
Other
functions
|
According
to Controller model
|
Ambient
operating temperature
|
-10 to
55ðC (with no condensation or icing)
|
Ambient
operating humidity
|
25% to
85%
|
Storage
temperature
|
-25 to
65ðC (with no condensation or icing)
|
Characteristics
|
|
Indication
accuracy
|
Thermocouple
: (+/-0.5% of indicated value or +/-1ðC,
whichever
greater)+/-1 digit max. (see note)
Platinum
resistance thermometer: (+/-0.5% of indicated value or
+/-1ðC, whichever greater)+/-1 digit
max.
Analog
input: +/-0.5% FS+/-1 digit max.
|
Hysteresis
|
0.1 to
999.9ðC (in units of 0.1ðC)
|
Proportional
band (P)
|
0.1 to
999.9ðC (in units of 0.1ðC)
|
Integral
time (I)
|
0 to
3999 s (in units of 1 s)
|
Derivative
time (D)
|
0 to
3999 s (in units of 1 s)
|
Control
period
|
1 to 99
s (in units of 1 s)
|
Manual
reset value
|
0.0% to
100.0% (in units of 0.1%)
|
Alarm
setting range
|
-1999 to
9999 (decimal point position depends on input type)
|
Input
sampling period
|
500ms
|
Insulation
resistance
|
20MΩ min.
(at 500 VDC)
|
Dielectric
strength
|
2000VAC,
50 or 60 Hz for 1 min (between different charging
terminal)
|
Vibration
resistance
|
10 to 55
Hz, 20m/s2 for 10 min in X, Y, Z directions
|
Shock
resistance
|
100 m/s2,
3 times each in 3 axes, 6 directions
|
Weight
|
Approx.
150g
|
Memory
protection
|
EEPROM
(non-volatile memory) (number of writes : 100,000)
|
EMC
|
Emission
Enclosure : EN55011(GB/T 6113.1,2) Group1 classA
Emission
AC Mains : EN55011(GB/T 6113.1,2) Group1 classA
Immunity
ESD : IEC61000-4-2(GB/T 17626.2)
4kV
contact discharge (level 2)
8kV air
discharge (level 3)
Immunity
RF-interference:IEC61000-4-3(GB/T17626.3):10V/m,
80MHz-1Ghz
(level 3)
Immunity
Conducted Disturbance : IEC61000-4-6(GB/T17626.6):
10V(0.15-80MHz)
(level 3)
Immunity
Burst: IEC61000-4-5(GB/T17626.5):2kV power-line (level 3)
2kV
signal-line (level 4)
|
Applicable
standards
|
UL61010C-1,
CSA C22.2 No.1010.1
Conforms
to EN61326, EN61010-1 (IEC61010-1)
|
Note: The indication of K thermocouples in the -200 to 1300ðC range, T and N thermocouples at
|
a temperature of -100ðC max., and U
and L thermocouples at any temperature is +/-2ðC
|
+/-1 digit maximum. The indication accuracy of the B thermocouples at
a temperature of
|
400ðC
max. is not specified. The indication of the R and S
thermocouples at a temperature
|
of 200 ðC max. is +/-3ðC+/-1 digit maximum.
|
|
|
|
|
|
|
|
|
|