MKS.TKS
|
MULTI-FUNCTION CONTROL
|
§ SMART TUNE ∙
PID CONTROL
|
§ UNIVERSAL, 3 WIRE ∙TC,
RTD AND LINEAR INPUT
|
§ 2 INDEPENDENT SET
POINT RAMP UP/DOWN PROFILES
|
§ SERVO VALVE
POSITIONER WITH POTENTIOMETER FEEDBACK
|
§ Ma CONTROL AND
RETRANSMISSION OUTPUT
|
§ PROCESS, BAND,
DEVIATION AND CONTROL FAULT ALARMS
|
§ RS 485 MODBUS
SERIAL COMMS OPTION
|
§ OPC BASED GRAPHICAL
CONFIGURATION SOFTWARE
|
§
IP 65 AND NEMA 4X FRONT PROTECTION
|
OVERVIEW
|
Designed
to offer outstanding performance and provide a comprehensive solution for a wide
variety of applications
|
such as; food processing, plastic manufacturing, and process
applications requiring heat/ cool control process protection alarms.
|
Additional
functionality includes; Servo valve positioner, (mA) linear control or retransmission output, CT input, ModBus
|
communication interface option, PC Configuration software.
|
Universal-thermocouple or RTD input coupled with a responsive SMART
auto-tuning PID control algorithm that is equipped with
|
special functions
including soft start and non linear cooling. A complete set of process
protection alarm function; high and low
|
limit, band and deviation are included.
|
The user
interface is a large, dual 4 digit LED display with output and status
beacons. Logic or Relay outputs are user
|
configurable as either control, timer status or alarm functions. A logic
input may be used to select up to 4 predefined operation
|
set-points. NEMA 4X & IP65 panel sealing allows these units to
be used in wash down or dusty applications.
|
PRODUCT SPECIFICATIONS
|
Case:
|
Polycarbonate
grey case
|
Self extinguishing degree:
|
According to UL 746 C.
|
Front
protection:
|
Designed
and tested for IP 65 (*) and NEMA 4X (*) for indoor locations
(when panel gasket is installed).
(*) In
accordance with IEC 529, CEI 70-1 and NEMA 250-1991 STD.
|
Weight:
|
360g max. for TKS model – 490g
max. for MKS model
|
Power
supply:
|
From 100
to 240V AC. 50/60Hz (+10% to -15% of the nominal value or 24V DC/AC
(+/-10%
of the nominal value).
|
Power consumption:
|
6VA max
|
Common
mode rejection ratio:
|
>
120dB @ 50/60Hz
|
Normal mode rejection ratio:
|
> 60dB @ 50/60Hz
|
EMC/Safety:
|
This
instrument is marked CE. It conforms to council directives 89/336/EEC
(reference
harmonized standard EN 50081-2 and EN 50082-2), 73/23/EEC and 93/68/EEC
(reference harmonized standard EN 61010-1).
|
Installation category:
|
II
|
Sampling
time:
|
250 mSec for linear inputs – 500 mSec
for TC or RTD inputs
|
Accuracy:
|
+0.2% f.s.v. @25๐C
(77๐F) and nominal power supply voltage
|
Operative
temperature:
|
From 0
to +50๐C
|
Storage temperature:
|
From -20 to +70๐C
|
Humidity:
|
From 20%
to 85% RH not condensing
|
HOW TO ORDER [MKS.TKS mA]
|
MODEL
|
OUTPUTS
|
OPTIONS
|
POWER
SUPPLY
|
CUSTOMISATION
|
MKS 1/4 DIN
TKS 1/8
DIN
|
9371 1mA output + 2 relay outputs
+
2 logic inputs + auxillary
power supply
|
2 Output 4
3 RS-485 + output 4
|
3 100/240V AC
5 24V AC/DC
|
000 Standard ERO Label
0B0 Blank – no manual
|
|
9371
|
|
|
|
|
|
|
|
|
|