Air
velocity and temperature transmitter
|
|
CTV 210
|
|
|
|
KEY POINTS
|
|
Configurable ranges from 0 to 30 m/s (model
with hot wire probe) and from 0 to 5 m/s (model with omnidirectional
probe)
|
Configurable range from 0 to 50๐C
in temperature
|
|
Airflow function
|
|
4 wires analogue output 0-5/10 V or
0/4-20 mA
|
|
Power supply 24 Vdc/Vac or 230 Vac (optional 115 Vac)
|
|
Trend indicator
|
|
ABS V0 IP65 housing, with or without display
|
|
1/4turn system mounting with
wall-mount plate
|
|
|
|
TECHNICAL FEATURES IN TEMPERATURE
|
|
Measuring
range
|
From
0 to +50๐C
|
|
Unit
of measurement
|
๐C/ ๐F
|
|
Accuracy
|
+/-0.3%
of reading +/-0.25๐C
|
|
Response
time
|
T90
= 0.9 second for Vair = 1 m/s
|
|
Resolution
|
0.1๐C/ 0.1๐F
|
|
Type
of sensor
|
Pt100
1/3 as per DIN IEC751
|
|
Type
of fluid
|
Air
and neutral gases
|
|
|
|
TECHNICAL FEATURES
IN AIR VELOCITY
|
|
Measuring
range
|
Standard
model: from 0 to 30 m/s
Omnidirectional model:
from 0 to 5 m/s
|
|
Unit
of measurement
|
m/s,
fpm, km/h
|
|
Accuracy
(standard and omnidirectional models)
|
Standard
model:
-
from 0 to 3 m/s : +/-3% of reading +/-0.03 m/s
-
from 3 to 30 m/s: +/-3% of reading +/-0.1 m/s
Omnidirectional model:
from 0 to 5 m/s: +/-3% of reading
+/-0.05 m/s
|
|
Resolution
|
Standard
model: from 0 to 3 m/s: 0.01 m/s and from 3 to 30 m/s: 0.1 m/s
Omnidirectional model:
from 0 to 5 m/s: 0.01 m/s
All
models: 1 fpm/ 0.1 km/h
|
|
Response
time
|
T63
= 1.6 s
|
|
Type
of fluid
|
Clean
air
|
|
|
|
TECHNICAL SPECIFICATIONS
|
|
Power
supply
|
|
24
Vac/Vdc +/-10%
|
|
230
Vac +/-10%, 50-60 Hz
|
|
115
Vac +/-10%, 50-60 Hz
|
|
|
|
Output
|
|
2
x 4-20 mA or 2 x 0-20 mA ou 2 x 0-5 V ou 2
|
|
x
0-10 V (4 wires)
|
|
Maximum
load: 500 Ohms (0/4-20 mA)
|
|
Minimum
load: 1 K Ohms (0-5/10 V)
|
|
|
|
Galvanic
isolation
|
|
Inputs
and outputs (models 115 Vac/230 Vac)
|
|
Outputs
(models 24 Vac/Vdc)
|
|
|
|
Consumption
|
|
5
VA
|
|
|
|
Electromagnetical compatibility
|
|
EN61326
|
|
|
|
Electrical
connection
|
|
Screw
terminal block for cable 2.5 mm2
|
|
|
|
PC
communication
|
|
Kimo USB-Mini
Din cable
|
|
|
|
Environment
|
|
Air
and neutral gases
|
|
|
|
Type
of fluid
|
|
Air
and neutral gases
|
|
|
|
Operating
temperature
|
|
From
0 to +50๐C
|
|
|
|
Storage
temperature
|
|
From
-10 to +70๐C
|
|
|
|
|
|
|