NON-CONTACT LOOP POWERED
|
|
ULTRASONIC LEVEL
TRANSMITTER
|
|
Simple, Fast Setup with Pushbutton
Calibration and LCD Display
|
|
Three Measurement Ranges Available up
to 10 m (32)
|
|
6-segment LCD Display Indicates Air Gap
or Liquid Level (Inch or Centimeter Units)
|
|
7.6 cm (3) Minimum Beam Width for
Applications with Restricted Space
|
|
NEMA 4X (IP65) Enclosure with Rugged
PVDF Transducer
|
|
Fail-Safe Intelligence with Diagnostic
Feedback for Easy Troubleshooting
|
|
The
LVU800 Series general purpose 2-wire ultrasonic transmitter provides
non-contact level
|
measurement
up to 10 m (32), and is ideally suited for challenging ultrapure,
corrosive or
|
|
waste liquids. Pushbutton calibrated, the
transmitter is broadly selected for atmospheric
|
|
bulk storage, day tank and waste sump applications.
Media examples include
|
|
wastewater and sodium hydroxide.
|
|
SPECIFICATIONS
|
|
Range:
|
LVU816:
|
10
cm to 5 m (4 to 16.4)
|
|
LVU826:
|
20 cm to 8 m (8 to 26.2)
|
|
LVU832:
|
30
cm to 10 m (12 to 32.8)
|
|
Accuracy:
|
+/-0.2% of span
|
|
Resolution:
|
LVU816/826:
|
1 mm (0.039)
|
|
LVU832:
|
2
mm (0.078)
|
|
Beam Width:
|
7.6 cm (3) dia.
|
|
Deadband:
|
LVU816:
|
10
cm (4)
|
|
LVU826:
|
20 cm (8)
|
|
LVU832:
|
30
cm (12)
|
|
Display Type:
|
LCD, 6-digit
|
|
Display
Units:
|
Inch,
cm or percent
|
|
Display Mode:
|
Air gap or liquid height
|
|
Memory:
|
Non-volatile
|
|
Supply Voltage:
|
12 to 28 Vdc
|
|
Loop Resistance:
|
500Ω
@24 Vdc
|
|
Signal Output:
|
4 to 20 mA, 2-wire
|
|
Signal
Invert:
|
4
to 20 mA or 20 to 4 mA
|
|
Calibration:
|
Pushbutton
|
|
Fail-Safety:
|
Selectable
4 mA, 20 mA, 21 mA, 22 mA or hold
|
|
Process Temperature:
|
-20 to 60๐C (-4 to 140๐F)
|
|
Temperature
Compensation:
|
Automatic
|
|
Electronics Temperature:
|
-40 to 71๐C (-40 to 160๐F)
|
|
Pressure:
|
30
psi (2 bar) @ 25๐C, derated @
1.667 psi (0.113 bar) per above 25๐C
|
|
Enclosure Rating:
|
NEMA 4X (IP65)
|
|
Enclosure
Vent:
|
Watertight
membrane
|
|
Enclosure Material:
|
PC/ABS FR
|
|
Transducer
Material:
|
PVDF
|
|
Process Mount:
|
2 NPT or 2
|
|
Mounting
Gasket:
|
FKM
|
|
Conduit Entrance:
|
Dual, ½ NPT
|
|
Classification:
|
General
purpose CE compliance EN 61326 EMC
|
|
|
|
|
|
|
|