S1
Series
|
5-kV and 10-kV Insulation Resistance Testers
|
CAT IV 600 V safety rating
|
Line supply or battery operated
|
Noise rejection (2mA or 4mA rms@200v and
above) for use in high voltage substations or switchyards
|
5mA output current provides fast charging and testing of
capacitive loads
|
Measurement range to 15 TΩ (5-kV models)
and 35 TΩ (10-kV models)
|
Automatic insulation resistance (IR),
dielectric absorption ratio (DAR), polarization index (PI), step voltage
(SV), and dielectric discharge (DD) tests
|
RS232 or USB download of results
|
On board memory for results storage
|
DESCRIPTION
|
The
new Megger S1 Series of 5 kV and 10 kV insulation
resistance testers are designed
|
specifically to assist the user with
the testing and maintenance of high voltage equipment.
|
This
series of testers includes the following models and distinct capabilities
including
|
voltage,
test current and noise rejection:
|
Model #
|
Outout Voltage
|
Test Current
|
Noise Rejection
|
S1-552/2
|
5 kV
|
5 mA
|
2 mA
|
S1-1052/2
|
10 kV
|
5 mA
|
2 mA
|
S1-554/2
|
5 kV
|
5 mA
|
4 mA
|
S1-1054/2
|
10 kV
|
5 mA
|
4 mA
|
All
four models are heavy duty and reliable with features that meet the most
demanding
|
testing applications in existence today.
|
APPLICATIONS
|
They
perform spot tests, step-voltage tests, and dielectric absorption tests for
the
|
following
applications:
|
Acceptance testing at an installation to check
conformance to specifications.
|
Routine preventive/ predictive maintenance
testing after installation.
|
Quality assurance testing as part of the manufacturing
process.
|
Diagnostic testing to isolate faulty
components for repair.
|
Contamination testing of service aged
insulation.
|
SPECIFICATIONS
|
|
Models
S1-552/2 and
S1-554/2
|
Models
S1-1052/2 and
S1-1054/2
|
Battery Life
|
6 hours
continuous testing
at 5kV
|
4 hours
continuous testing
at 10kV
|
Test
Voltages
|
50 V to 1 kV in 10V
steps
1 kV to 5 kV in 25V
steps
|
50 V to 1 kV in 10V
steps
1 kV to 10 kV in 25V
steps
|
Accuracy
|
+/-5% to 1
TΩ
+/-20% to
10 TΩ
|
+/-5% to 2
TΩ
+/-20% to
20 TΩ
|
Display Range
-
Digital Display (3 digit)
-
Analog Display
|
10 kΩ to 15 TΩ
100 kΩ to 1 TΩ
|
10 kΩ to 35 TΩ
100 kΩ to 1 TΩ
|
Capacitor Charge Time
|
< 1.5
seconds per µF
at 5mA to
5kV
|
< 3
seconds per µF
at 5mA to
10kV
|
Capacitor
Discharge Time
|
< 120ms per µF
to discharge from
5000V to 50V
|
< 250ms per µF
to discharge from
10000V to 50V
|
Display:
|
Analog/digital 3 digits
|
Interference
rejection:
|
2
mA rms @ 200 V and above
(S1-552/2 and S1-1052/2)
4
mA rms @ 200 V and above
(S1-554/2 and
S1-1054/2)
|
Filter (models S1-554/2 and S1-1054/2 only)
|
10, 30 and 100 second time constants (selectable)
|
Timer
range:
|
Up
to 99 minutes and 59 seconds from start of test
|
Memory capacity:
|
32kB
|
Temperature Range:
|
Operating:
|
-4๐F to 122๐F (-20๐C to +50๐C)
|
Storage:
|
-13๐F to 149๐F (-25๐C to +65๐C)
|
Humidity:
|
90%
RH non-condensing at 40๐C
|
Safety:
|
Meets the requirements of EN61010-1:2001 CATIV 600 V
|
EMC
|
Meets
the requirements of EN61326-1:1998 for use in heavy industrial areas
|
Dimensions:
|
12.7 x 6 x 14.2 inch (305 x 194 x 360 mm)
|
Weight:
|
16
lb (7.1 kg) approx.
|
|
|
|
|
|
|