WL700 Ultrasonic Level
Sensor
|
|
Non-Contact
Water Level Measurement
|
|
·
Non-Contact Measurement
|
|
·
Rugged and Fully Encapsulated
|
|
·
4-20 ma Transmitter
|
|
·
Easy Installation/ No Programming
|
|
·
Cost Effective
|
|
·
Great for Wastewater
|
|
·
Great for Flumes and Weirs
|
|
·
Temperature Compensated
|
|
·
Three Ranges: 1’, 3’ and 6’
|
|
·
For Monitoring Water Level and Open Channel Flow
|
|
The
WL700 uses the latest ultrasonic distance measuring technology for accurate
non-contact
|
|
water level monitoring. The fully encapsulated sensor/
transmitter is temperature compensate
|
|
and provides an industry standard 4-20 MA
output. There are three ranges available including
|
|
1’,
3’ and 6’ to meet a wide variety of applications. The unique
1’ range sensor is ideal for
|
|
measuring flow in small flumes and weirs. The 3’ and
6’ ranges are best for measuring river, lake
|
|
and tank levels and for measuring open channel flow in
larger flumes. Installation is simple and
|
|
requires no programming or calibration. No maintenance is
required.
|
|
The WL700 Ultrasonic Level Sensor is rugged, reliable and
completely weatherproof. It is ideal for
|
|
sewer or wastewater applications. The
sensor is easy to mount, comes with a 10’ cable and
|
|
complete instructions. It is
easy to interface to all PLC’s, SCADA and
telemetry systems with its
|
|
simple 3-wire 4-20 MA output. The WL700 is
compatible and provided optionally with the Global
|
|
Water FC200 Open Channel Flow Monitor and the PC300 Process Controller
(for water level control).
|
Specifications
|
|
Ranges:
|
0.2’
to 1’; 0.4’ to 3’; 0.8’ to 6’; and 1.5’
to 35’
|
Input:
|
18 to 30 VDC
|
Current Draw:
|
100 ma
|
Output:
|
4-20 ma (4
ma is minimum water level and 20 ma is maximum water level)
|
Averaging:
|
15 second running average (to smooth out water turbulence).
|
Warm Up Time:
|
15 seconds
|
Resolution:
|
Continuous
Analog
|
Operating Temperature
Range:
|
-40๐ to
+185๐F (-40๐
to 85๐C) (1, 3, and 6 ft range);
-40๐ to
+145๐F (-40๐
to 62๐C) (35 ft range only)
|
Temperature Compensated Range:
|
-20F to 120F
|
Accuracy:
|
+/-1.0%
of Range, +/-2.0% of 35 ft Range
|
Dimensions:
|
1 x 2 x 4 inches (2.5 x 5.1 x 10.2 cm) rectangular (1 ft
range)
1 inch id pipe thread x 4 inches long (2.5 cm ID x 10.2 cm
long) (3 ft and 6 ft range)
2-1/2 inches id pipe thread x 4 inches long (6.3 cm ID x 10.2
cm long) (35 ft range)
|
Material:
|
Extruded Aluminum (1’ range), PVC (3’, 6’
and 35’ range)
|
Weight:
|
1.5 Lbs
|
|
|
|