1480
1/8 DIN
|
Panel
Indicator
|
|
Features
|
· Universal
Input (Strain Gauge, Voltage, Current, Thermocouple or RTD)
|
· Min/max
Value Hold
|
· 2 Alarm
Outputs
|
· Retransmission
|
|
Description
|
The
1480 is a Universal Pressure or Temperature Input Indicator with single or
dual configurable
|
alarms, as well
as optional linear retransmission of displayed Process Variable. Ideal for
use in
|
Extrusion
applications.
|
|
Specifications
|
PERFORMANCE CHARACTERISTICS
|
Output
Configuration
|
1
or 2 relay outputs, with optional linear retransmission
|
Alarms
|
2
process high/low with adjustable hysteresis
|
Viewable
Values
|
Process
variable, maximum value, minimum value
|
Legends
|
๐C/ ๐F LED
|
Human
Interface
|
3
button operation, 4 digit 13mm high display red, green or red/green
(color
change on alarm), plus 1 set-up, 2 alarm indicator
|
Input
Thermocouple
|
J,
K, C, R, S, T, B, L, N
|
RTD
|
3
Wire PT100, 50Ω per lead maximum (balanced)
|
Strain
Gauge
|
350
Ohm Strain Gage
|
DC
Linear
|
0
to 20mA, 4 to 20mA, 0-50mV, 10-50mV,
0
to 5V, 1 to 5V, 0 to 10V, 2 to 10V
Note:
24V external power supply required
|
Input
Impedance
|
>10MΩ
for thermocouple and mV ranges, 47kΩ for V ranges and 5Ω for mA ranges
|
Accuracy
|
+/-0.1%
of input range +/-1 LSD (T/C CJC better than 1๐C)
|
Sampling
|
4
per second, 14 bit resolution approximately (250ms sample time)
|
Sensor
Break Detection
|
<2
seconds (except zero based DC ranges), high alarms activate for T/C RTD,
Strain
Gauge and mV ranges, low alarms activate for mA or V ranges
|
|
OUTPUTS & OPTIONS
|
Alarm
Relays
|
Contacts
Single Relay SPDT 2 Amp resistive at 240VAC, > 500,000 operations.
Latching
or non-latching. Dual Relay SPST 2 Amp resistive at 240V >200,000
operations. Reinforced safety isolation from inputs and other outputs.
|
|
DC LINEAR RETRANSMIT
|
Outputs
|
0
to 20mA, 4 to 20mA into 500Ω max, 0 to 10V, 2 to 10V, 0 to 5V into 500Ω min.
Accuracy
+/-0.25% at 250Ω (degrades linearly to 0.5% for increasing burden to specified
limits)
|
Logic
Input
|
External
reset of latched relay, stored alarm 1 elapsed time, stored min/max PV values
or initiate tare function. Action occurs on high (3 to 5VDC) to low
<0.8VDC, or Open to Closed transition
|
|
OPERATING & ENVIRONMENTAL
|
Temperature
& RH
|
0
to 55๐C
(-20 to 80๐C
storage), 20% to 95% RH non-condensing
|
Power
Supply
|
85
to 264V 50/60Hz 7.5VA (optional 20 to 48V AC 7.5VA/22 to 65V DC 5 watts)
|
Front
Panel Protection
|
IEC
IP66 (Behind panel protection is IP20)
|
Standards
|
CE.