MIT510/2, MIT520/2 and MIT1020/2
|
|
5-kV
and 10-kV Insulation Resistance Testers
|
|
Line supply or battery operated
|
|
Digital/analog backlit display
|
|
Measurement range to 15 TΩ (MIT510/2
and MIT520/2) and 35 TΩ (MIT1020/2)
|
|
CAT IV 600 V safety rating
|
|
Automatic dielectric absorption ratio,
polarization index, step voltage, and dielectric discharge tests (MIT520/2 and
MIT1020/2)
|
|
RS232 or USB download of results (MIT520/2
and MIT1020/2)
|
|
Ingress protection to IP65
|
|
3 mA short
circuit current
|
|
APPLICATIONS
|
|
All
three models are designed for testing the insulation of high-voltage electric
equipment.
|
|
Their
wide voltage range also allows applications for low-voltage equipment. Generators,
|
|
motors, transformers, cables and switchgear
all require effective maintenance. The test
|
|
techniques on the instruments provide valuable
diagnostic information.
|
|
|
|
All
three instruments test the insulation resistance of:
|
|
High-voltage power cables and
high-voltage buses
|
|
Large motor/generator windings
|
|
Line and substation transformers
|
|
SPECIFICATIONS
|
|
Test Voltage
|
|
MIT510/2: 250 V, 500 V, 1000 V,
2500 V, 5000 V
|
|
MIT520/2: 50 V to 1 kV in 10 V
steps, 1 kV to 5 kV in 25 V steps
|
|
MIT1020/2: 50 V to 1 kV in 10 V
steps, 1 kV to 10 kV in 25 V steps
|
|
|
|
Insulation Resistance Range
|
|
Digital
display:
|
|
MIT510/2
and MIT520/2: 10 kΩ to 15 TΩ
|
|
MIT1020/2:
10 kΩ to 35 TΩ
|
|
Analog
display:
|
|
MIT510/2,
MIT520/2 and MIT1020/2: 100 kΩ to 1 TΩ
|
|
|
|
Accuracy (23๐C)
|
|
+/-5%
to 1 TΩ
|
|
+/-20%
to 10 TΩ (MIT520/2)
|
|
+/-20%
to 20 TΩ (MIT1020/2)
|
|
|
|
Voltage Output Accuracy (0๐C to 30๐C)
|
|
0
to +4% +/-1V of nominal test voltage at 100 MΩ load
|
|
+/-25
V for test voltages less than 500 V
|
|
|
|
Short Circuit/Charge Current
|
|
3
mA
|
|
|
|
Current Measurement
|
|
Range: +/-0.01 nA to +/-5 mA
|
|
Accuracy
(23๐C): +/-5% +/-0.2 nA at all voltages
|
|
|
|
Capacitance Measurement
|
|
Range: 10 nF
to 50 µF (for voltages > 500 V)
|
|
Accuracy
(23๐C): +/-5% +/-5 nF
|
|
|
|
Capacitor
|
|
Charge
Time:
5 seconds per µF at 3 mA
|
|
Discharge
Time:
5 seconds per µF to discharge from:
|
|
MIT510/2
and MIT520/2: 5000 V to 50 V
|
|
MIT1020/2:
10,000 to 50 V
|
|
|
|
Display
|
|
Analog/digital
3 digits
|
|
|
|
Timer Range
|
|
Count
up to 99 minutes and 59 seconds from start of test
|
|
|
|
Voltage Input Range
|
|
95
to 240 V, +/-10% rms 50/60 Hz and dc
|
|
|
|
Battery Life
|
|
6
hours continuous testing at 5 kV
|
|
4
hours continuous testing at 10 kV
|
|
|
|
Ingress Protection
|
|
IP65
(lid closed)
|
|
|
|
Temperature Range
|
|
Operating: -4๐F to +122๐F (-20๐C to +50๐C)
|
|
Storage: -13๐F to +149๐F (-25๐C to +65๐C)
|
|
|
|
Humidity Range
|
|
90%
RH @ 104๐F (40๐C)
|
|
|
|
Dimensions
|
|
12
in. x 7.6 in. x 14.2 in. (305 mm x 194 mm x 360 mm)
|
|
|
|
Weight
|
|
15
lb. (6.75 kg)
|