The ELITEproTM
includes 4 channels of current (0-6000 A), and 3 channels of voltage (0-600V
|
|
ac or dc). It measures Volts, Amps, Watts,
Volt-Amps (VA), Volt-Amps Reactive (VAR), Power
|
|
Factor, and Harmonics (1st-63rd).
|
|
ELITEproTM features include:
|
|
kWh, Volts, Amps, kVA, kVAr, and power factor
recording for single-phase and three-phase loads
|
|
128K of memory
(~25,000 records) or 512K (~100,000 records)
|
|
Battery powered, no cords to plug-in
|
|
Remote downloading using an
internal modem (optional)
|
|
New expanded features include:
|
|
Power Quality:
harmonics & waveform capture
|
|
Automatic data
collection using dial-in or dial-out
|
|
Internal modem
capability
|
|
Alarm capability
|
|
Easy Installation
|
|
The ELITEproTM
can easily fit inside most electrical cabinets, which eliminates problems
|
|
associated with external metering. It weighs only 0.7 Kg (21 ounces), excluding
cables and sensors.
|
|
Dimensions are: 8 x 15 x 6 cm
(3.2” x 5.9” x 2.4”)
|
|
Weather-Tight option: 17.1 x 12.1
x 8.3 cm (6.75” x 4.75” x 3.25”)
|
|
ELITEproTM Accessory Package (optional) comes with ELOG software,
null-modem communication cable,
|
|
and an operation manual.
|
|
POWER MONITORING SPECIFICATIONS
|
|
The ELITEproTM
can monitor up to: four single-phase, 2 wire loads or two three-phase, 3 wire
loads,
|
|
or one three phase, 4 wire load. A variety of voltage taps and current
transformers are available.
|
|
Inputs
|
4 channels of current, 0-6000A
3 channels of voltage, 0-600 V ac or dc
|
|
Power
|
Volts, Amps, Watts,
Volt-Amps, Volt-Amps-Reactive, Power Factor
|
|
Measurements
|
True RMS
|
|
Frequency
|
50 or 60 Hz
|
|
Accuracy
|
< 1% of reading exclusive of sensor accuracy
|
|
Baud Rate
|
1200 – 57,600
|
|
Resolution
|
12 bit (1 part in 4,096); 0.1 Volt, 0.01 Amp, 1 Watt,
1 VAR, 1 VA, 0.01 PF
|
|
Memory
|
128k (25,000 readings) or
512k (100,000 readings)
|
|
Sampling Frequency
|
7.68 kHz (128 points per waveform)
|
|
Recording Intervals
|
3, 15, 30 seconds; 1, 5, 15, 30,
60 minutes; and 12, 24 hours
|
|
Recording Events
|
Average, minimum and maximum
|
|
Real Time Clock
|
20 ppm
accuracy (< 1min/month)
|
|
Operating Temperature
|
-7๐ to 60๐C (20๐ to 140๐F)
|
|
Battery Life
|
3-10 years @ 1 min. sampling, with
LED indicator of low battery charge
|
|
Harmonic Analysis
|
To the 63rd Harmonic
|